LUGB Intelligent Vortex Air/Gas Flow meter
The series of Vortex Flowmeter is based on Carmen Vortex Principle, which adopts piezoelectric crystal as testing
components. It is a new kind of stress detecting vortex flowmeter. It has the advantages of wide range rate, high
accuracy, low pressure loss, good medium generality, pulse signal output proportional to flow, convenient to
connect with computer etc. The detector probe of sensor and the vortex generating body are installed separately,
and the high temperature resistant piezoelectric crystal doesn't contact with medium, so the instrument is simple
structure, good generality, and high stability.
LUGB series Vortex Flowmeter sensor can be used to detect and measure the flow of all kinds of gas, fluid and
steam.
LUGB flowmeter sensor can be used to match with our company's MT6000 series flow totalizer. It also can match
with computers and sensors of temperature, pressure, or density to compose high accuracy mass flow or heat flow detecting and measuring system.
Technical Parameters
Measured medium: all kinds of gas, fluid and steam
Nominal diameter:20-300mm (ontology-type) 300-1000mm (Insertion type)
Operating environment: Environment temperature -40°c~55°c Relative humidity:≤90%
Nominal Pressure: 1.6Mpa 2.5Mpa 4.0Mpa
Measurement Range: gas and steam: 4.5-45m/s fluid: 0.45-4.5 m/s
Measurement Accuracy: ±0.5% ±1%
Output Signal: Pulse signal (current or voltage pulse) LUGB series- A
Current signal (4-20mA) LUGB series-B
Safety Protection: intrinsically-safe explosion-proof type explosion-proof level: ia II CT1-6
Anti-corrosion type (Suitable for measuring corrosive medium)
Power Supply: DC24V
Mounting Method: Flange-collection-type, flange- Card-type, insert-type
Photo copyright reserved!